Liebert Universal Monitor Bedienungsanleitung

Stöbern Sie online oder laden Sie Bedienungsanleitung nach Prozessoren Liebert Universal Monitor herunter. Liebert Universal Monitor User's Manual Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 144
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen

Inhaltsverzeichnis

Seite 1 - UNIVERSAL MONITOR

MONITORINGUNIVERSAL MONITOR USER MANUAL

Seite 2 -

Introduction21.5 Outside Enclosure OverviewThe enclosure for the Universal Monitor’s controller board comes in two sizes:•The large enclosure is desig

Seite 3 - TABLE OF CONTENTS

View Status Menus92A.4 VIEW STATUS MENUS The View Status menu allows any user to view currently active alarms, monitoring data stored in the alarm, ev

Seite 4 - 7.0 VIEW STATUS OPTIONS

View Status Menus93A.4.1 View Active Alarms For details on this feature, see 7.1 - View Active Alarms. View Active AlarmsACTIVE ALARMSInput points/har

Seite 5 - 10.0 SPECIFICATIONS

View Status Menus94A.4.2 View Alarm LogFor details on this feature, see 7.2 - View Alarm Log.View Alarm LogALARM LOGAlarm historySENSOR_2 80.0 DEGH

Seite 6

View Status Menus95A.4.3 View Event LogFor details on this feature, see 7.3 - View Event Log.View Event LogEVENT LOGEvent historyPAGERUNSUCCESSFUL PAG

Seite 7

View Status Menus96A.4.4 View Trend LogFor details on this feature, see 7.4 - View Trend Log.View Trend LogTREND LOGTrend historyfor each sensorSelect

Seite 8

View Status Menus97A.4.5 View Input StatusFor details on this feature, see 7.5 - View Input Status.View Input & Sensor StatusINPUT & SENSOR ST

Seite 9 - 1.0 INTRODUCTION

View Status Menus98A.4.6 View Output StatusFor details on this feature, see 7.6 - View Output Status.View Output StatusOUTPUT STATUSDiscrete outputs s

Seite 10 - Universal Monitor

View Status Menus99A.4.7 View Pager NumbersFor details on this feature, see 7.7 - View Pager Numbers.View Pager NumbersPAGER & PIN NUMBERSNumbers

Seite 11 - 1.6 Typical Configuration

Silence Alarm & Back Up Log Files (Service Terminal Interface only)100A.5 SILENCE ALARM & BACK UP LOG FILES (SERVICE TERMINAL INTERFACE ONLY)T

Seite 12 - ALL CIRCUITS:

Silence Alarm & Back Up Log Files (Service Terminal Interface only)101A.5.2 Back Up Log Files (Service Terminal Interface only) For details on thi

Seite 13

Introduction31.6 Typical ConfigurationFigure 3 shows an example of external devices connected to the Universal Monitor’s controller board. There may b

Seite 14 - RELAY OUTPUTS

Silence Alarm & Back Up Log Files (Service Terminal Interface only)102Back Up Event Log FileBackup Log Files - Event Log FileBACKUP LOG FILESBacku

Seite 15 - 1.9 LED Indicators

Silence Alarm & Back Up Log Files (Service Terminal Interface only)103Back Up Trend Log FilesBackup Log Files - Trend Log FilesBACKUP LOG FILESBac

Seite 16 - K4K3K2K1 K5 K6 K7 K8

Setup Menu104A.6 SETUP MENUThe Setup menu allows the user to configure the Universal Monitor—setting up inputs and outputs and an input/output matrix

Seite 17 - 1.11 Typical Sequence

Setup Menu105Setup Menu This section presents Service Terminal Interface screens for each of the following:* Setup System Information features are:• C

Seite 18 - 2.0 INSTALLATION - MAIN BOARD

Setup Menu106A.6.1 Setup InputFor details on this feature, see 9.3 - Setup System - Setup Input.Setup Input - Main Board OutputsSETUP INPUTSetup for d

Seite 19 - 2.2.1 Mounting the Panel

Setup Menu107Setup Input - Expansion Board InputsSETUP INPUTSetup for discreteinput pointsSelect input to editINPUT DEFINITION1=INPUT_01 NO-EV-NL-00:

Seite 20 - 2.3.1 Mounting the Panel

Setup Menu108A.6.2 Setup Common AlarmFor details on this feature, see 9.4 - Setup System - Setup Common Alarm.Setup Common AlarmSETUP COMMON ALARMSele

Seite 21

Setup Menu109A.6.3 Setup SensorFor details on this feature, see 9.5 - Setup System - Setup Sensor.Setup SensorSETUP SENSORSetup for analoginput points

Seite 22 - Input Power Connections

Setup Menu110>[>COMMAND SUCCESSFUL>CHANGE OFFSET VALUE.>[000.0]>[>COMMAND SUCCESSFUL>IS SENSOR AN ALARM(AL) OR EVENT(EV)?>[AL]

Seite 23

Setup Menu111A.6.4 Setup I/O MatrixFor details on this feature, see 9.6 - Setup System - Setup I/O Matrix.Setup I-O Matrix - Map Input to Output - Mai

Seite 24 - Packing Contents

Introduction41.7 Controller Board OverviewThe Universal Monitor’s controller board has connectors for eight digital inputs, four analog inputs and eig

Seite 25 - 3.2.1 Mounting the Panel

Setup Menu112>[>COMMAND SUCCESSFUL>MAP INPUT_01 TO OUTPUT06-YES(Y) OR NO(N)?>[N]>[>COMMAND SUCCESSFUL>MAP INPUT_01 TO OUTPUT07-YE

Seite 26 - 3.3.1 Mounting the Panel

Setup Menu113Setup I-O Matrix - Map Input to Output - Expansion Board InputsSETUP I/O MATRIXProgram inputs & sensorsto control outputsSelect to ma

Seite 27

Setup Menu114>MAP INPUT_09 TO OUTPUT01-YES(Y) OR NO(N)?>[Y]>[>COMMAND SUCCESSFUL>MAP INPUT_09 TO OUTPUT02-YES(Y) OR NO(N)?>[N]>[&

Seite 28 - 4.1 Wiring Specifications

Setup Menu115Setup I-O Matrix - Map Sensor to OutputSETUP I/O MATRIXProgram inputs & sensorsto control outputsSelect to map inputs or sensors1=MAP

Seite 29 - (BOTTOM)

Setup Menu116>[>COMMAND SUCCESSFUL>MAP SENSOR_1 HIGH STPT TO OUTPUT06-YES(Y) OR NO(N)?>[N]>[>COMMAND SUCCESSFUL>MAP SENSOR_1 HIGH

Seite 30 - 4.3 Connecting Analog Inputs

Setup Menu117A.6.5 Setup OutputFor details on this feature, see 9.7 - Setup System - Setup Output.Setup Output - Main Board OutputsSETUP OUTPUTSetup f

Seite 31 - TB10: COMMS

Setup Menu118Setup Output - Expansion Board OutputsSETUP OUTPUTSetup for discreteoutput pointsSelect output to editOUTPUT DEFINITION1=OUTPUT01 NO2=OUT

Seite 32 - 4.6.2 Phone Line Connector

Setup Menu119A.6.6 Setup Modem & PagersFor details on this topic, see 9.8 - Setup System - Setup Modem & Pagers.Pager SetupFor details on this

Seite 33 - 5.1 Wiring Specifications

Setup Menu120Modem SetupFor details on this feature, see 9.8.1 - Modem Setup - Initialization String and 9.8.2 - Modem Setup - Additional Features (Se

Seite 34 - EIA485 - (to UM+)

Setup Menu121A.6.7 Setup System InfoThis section presents Service Terminal Interface screens for choices 1 through 9 in the Setup System Information m

Seite 35 - POWER INPUT RELAY OUTPUTS

Introduction5K - Digital output loss-of-power jumperOne of eight output jumpers. Each digital output has a jumper to set the fail-safe position of the

Seite 36

Setup Menu122Change Date & Time/Automatic Daylight Saving TimeFor details on this feature, see 9.9.2 - Change Date & Time/Automatic Daylight S

Seite 37

Setup Menu123Connect Battery For details on this feature, see 9.9.4 - Connect Battery.Backup and Upload Configuration File (Service Terminal Interface

Seite 38 - 6.0 OVERVIEW OF MENUS

Setup Menu124Setup Service Phone Number For details on this feature, see 9.9.6 - Setup Serv Ph Num - Enter Phone Number and 9.9.7 - Setup Serv Ph Num

Seite 39 - 6.3 LCD Menu Overview

Setup Menu125Factory Defaults For details on this feature, see 9.9.8 - Factory Defaults.Firmware Update (Service Terminal Interface only)For details o

Seite 40

Setup Menu126Initiate Remote Alarm Test (Service Terminal Interface only)For details on this feature, see 9.9.10 - Initiate Remote Alarm Test (Service

Seite 41 - 7.1 View Active Alarms

Setup Menu127A.6.8 Connect Expansion BoardFor details on this feature, see 9.10 - Setup Exp Board - Optional Expansion Board.Connect Expansion BoardCO

Seite 42 - 7.2 View Alarm Log

Setup Menu128A.6.9 Override Output For details on this feature, see 9.11 - Manual Output Ctrl.Override Output - Main Board OutputsOVERRIDE OUTPUTManua

Seite 43 - 7.3 View Event Log

Setup Menu129Override Output - Expansion Board OutputsOVERRIDE OUTPUTManually overridean output pointSelect output to overrideOUTPUT CONTROL1=OUT

Seite 44 - 7.4 View Trend Log

Setup Menu130A.6.10 Clear Alarms & LogsFor details on this topic, see 9.12 - Clear Alarms & Logs.Clear Active AlarmsFor details on this featur

Seite 45 - 7.5 View Input Status

Setup Menu131Clear the Event Log For details on this feature, see 9.12.3 - Clear the Event Log.Clear the Trend LogsFor details on this feature, see 9.

Seite 46 - 7.6 View Output Status

Introduction61.8 Optional Expansion Board OverviewThe Universal Monitor Expansion Board, purchased separately, has connectors for 16 digital inputs an

Seite 47 - 7.7 View Pager Numbers

Default Settings Quick Reference Guide132APPENDIX B- DEFAULT SETTINGS QUICK REFERENCE GUIDEThis appendix provides a quick reference to default setting

Seite 48

Default Settings Quick Reference Guide133Table 38 Universal Monitor - other default settingsJUMPER SETTINGSFeature Default Other OptionsDigital output

Seite 49

Default Settings Quick Reference Guide134Table 39 Expansion Board - default settings for inputs and outputsDEFAULT SETTINGS - DIGITAL INPUTS (FROM TAB

Seite 51 - 9.1 Login

The Company Behind the ProductsWith over a million installations around the globe,Liebert is the world leader in computer protectionsystems. Since its

Seite 52 - ↵ =NEXT/END

Introduction71.9 LED IndicatorsThe Universal Monitor’s controller board has LED indicators that show the status of inputs, outputs and the common alar

Seite 53 - 9.2 Setup System - Overview

Introduction81.10 LED Indicators - Optional Expansion BoardThe optional Expansion Board, purchased separately, has LED indicators that show the status

Seite 54

Introduction91.11 Typical SequenceFigure 4 shows a typical sequence of how the Universal Monitor functions after detecting a change in a monitored uni

Seite 55 - 9.3.5 Set Up Delay Time

Installation - Main Board102.0 INSTALLATION - MAIN BOARDThis section provides instructions for installing, mounting and connecting power to the Univer

Seite 56

Installation - Main Board112.2 Surface-Mounting the Universal MonitorAfter determining where to place the unit, check to ensure that you have all the

Seite 58 - 9.5.3 Change Units Label

Installation - Main Board122.3 Flush-Mounting the Universal MonitorThe Universal Monitor may be flush-mounted according to company practices—either wi

Seite 59 - 9.5.6 Change Offset Value

Installation - Main Board132.4 Connect Power to the Universal MonitorThe Universal Monitor requires 24VAC for proper operation. Liebert recommends usi

Seite 60

Installation - Main Board142.4.2 Termination and Mounting - Large EnclosureInput Power ConnectionsTo connect electrical power to the Transformer Modul

Seite 61 - 9.5.10 Change High Setpoint

Installation - Main Board15Troubleshooting - Transformer ModuleA common problem and possible solution are shown in the table below. For further inform

Seite 62 - 9.5.11 Set Up Delay Time

Installation - Optional Expansion Board163.0 INSTALLATION - OPTIONAL EXPANSION BOARDThis section provides instructions for installing, mounting and co

Seite 63

Installation - Optional Expansion Board173.2 Surface-Mounting the Optional Expansion BoardAfter determining where to place the optional Expansion Boar

Seite 64

Installation - Optional Expansion Board183.3 Flush-Mounting the Optional Expansion BoardThe optional Expansion Board may be flush-mounted according to

Seite 65

Installation - Optional Expansion Board193.4 Input Power Connections - Optional Expansion BoardThe optional Expansion Board requires 24VAC for proper

Seite 66

Wiring and Connections - Main Board204.0 WIRING AND CONNECTIONS - MAIN BOARD4.1 Wiring SpecificationsInput and output connections to the Universal Mon

Seite 67

Wiring and Connections - Main Board214.2 Connecting Digital Inputs and Digital OutputsThe digital inputs and digital outputs are found on the lower ri

Seite 68 - Configuring the Modem

iTABLE OF CONTENTS1.0 INTRODUCTION1.1 Methods of Viewing and Configuring the Universal Monitor . . . . . . . . . . . . . . . . . . . . . . . . . 11.2

Seite 69

Wiring and Connections - Main Board224.2.3 Setting the Digital Output JumpersEach digital output has an associated jumper to define its operation when

Seite 70

Wiring and Connections - Main Board234.3.1 Setting the 12VDC/24VDC Analog Power JumperThe analog power jumper sets the common voltage that is applied

Seite 71

Wiring and Connections - Main Board244.4 Connecting Common Alarm OutputsThe common alarm relay, found in the top right corner of the Uni-versal Monito

Seite 72

Wiring and Connections - Optional Expansion Board255.0 WIRING AND CONNECTIONS - OPTIONAL EXPANSION BOARD5.1 Wiring SpecificationsInput and output conn

Seite 73

Wiring and Connections - Optional Expansion Board265.2 Connecting Inputs and OutputsThe Universal Monitor’s optional Expansion Board permits the addit

Seite 74

Wiring and Connections - Optional Expansion Board275.2.2 Connecting Digital OutputsThe eight digital outputs are found at the top of the Expansion Boa

Seite 75

Wiring and Connections - Optional Expansion Board285.2.3 Setting the Digital Output DIP SwitchesEach digital output on the optional Expansion Board ha

Seite 76

Wiring and Connections - Optional Expansion Board295.3 Connect to the Universal MonitorTwo steps are required to establish connection between the opti

Seite 77 - Change the Password

Overview of Menus306.0 OVERVIEW OF MENUSThere are two ways to access the Universal Monitor: the LCD on the front of the enclosure and the Service Term

Seite 78 - 9.9.4 Connect Battery

Overview of Menus316.1 Opening Screen OverviewThe Universal Monitor displays the Opening Screen at startup, as shown in Figure 12.• If any alarms are

Seite 79

ii5.0 WIRING AND CONNECTIONS - OPTIONAL EXPANSION BOARD5.1 Wiring Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Seite 80

View Status Options327.0 VIEW STATUS OPTIONSThe View Status menu allows any user to view currently active alarms, monitoring data stored in the alarm,

Seite 81

View Status Options337.1 View Active AlarmsThe Active Alarm screen displays all alarms that are occurring, up to a maximum of 33.A Current Alarm scree

Seite 82

View Status Options347.2 View Alarm LogThe Alarm Log contains up to 99 records of alarms that have occurred. Records are added to this log as alarms o

Seite 83

View Status Options357.3 View Event LogIn addition to alarms, the Universal Monitor tracks other changes in the Event Log to assist users with verifyi

Seite 84 - 9.9.8 Factory Defaults

View Status Options367.4 View Trend LogThe Universal Monitor takes readings of configured analog input sen-sors at regular intervals and stores them i

Seite 85

View Status Options377.5 View Input StatusThe Input Status option allows you to view the current status of all inputs: the four analog sensor inputs a

Seite 86

View Status Options387.6 View Output StatusThe Output Status option allows you to view the current status of all eight outputs. If the optional Expans

Seite 87

View Status Options397.7 View Pager NumbersThe Universal Monitor may be set up to dial pager numbers when an alarm is detected. Up to four pagers may

Seite 88 - 9.11 Manual Output Ctrl

Silence Alarm & Backup Log Files (Service Terminal Interface)408.0 SILENCE ALARM & BACKUP LOG FILES (SERVICE TERMINAL INTERFACE)This section d

Seite 89 - 9.12 Clear Alarms & Logs

Silence Alarm & Backup Log Files (Service Terminal Interface)418.2 Back Up Log Files (Service Terminal Interface only)The Universal Monitor mainta

Seite 90 - 9.12.4 Clear the Trend Logs

iii9.5 Setup System - Setup Sensor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 499.5.1 Identif

Seite 91

Silence Alarm & Backup Log Files (Service Terminal Interface)425. At the top of the HyperTerminal window, shown below, click on Transfer, then on

Seite 92

System and Control Options439.0 SYSTEM AND CONTROL OPTIONSThe System and Control menu allows you to configure the Universal Monitor—setting up inputs

Seite 93 - Service Terminal Interface

System and Control Options44Figure 14 shows the main options available from the System & Control menu.Figure 14 Menu overview - System and Control

Seite 94 - A.2.1 Connection Methods

System and Control Options459.2 Setup System - OverviewThe Setup System screen displays seven options that allow you to configure input and output dev

Seite 95 - A.2.2 Create a Connection

System and Control Options469.3.1 Change Label (Name of Input)Each input has a default label (Input_01, Input_02, etc.) that you may change to a more

Seite 96 - COM1 Port Setup

System and Control Options479.3.4 Set Up Alarmable Inputs in Latched or Unlatched ModeAlarmable input points may be set up in Latched mode (Y), which

Seite 97 - ASCII Setup

System and Control Options489.4 Setup System - Setup Common AlarmThe audible alarm sounds after the Universal Monitor detects an alarm condition in an

Seite 98

System and Control Options499.5 Setup System - Setup SensorThe Universal Monitor has four analog sensor input points that may be configured individual

Seite 99 - A.3 OVERVIEW OF MENUS

System and Control Options509.5.1 Identify the Sensor as ConnectedTo make use of an analog sensor, you must specify it as Connected (Y). By default, a

Seite 100 - A.4 VIEW STATUS MENUS

System and Control Options519.5.4 Change 4 mA ValueFor the 4 mA value, enter the smallest value for the range of the sen-sor—for example, 50°F for a t

Seite 101 - A.4.1 View Active Alarms

ivAPPENDIX A-SERVICE TERMINAL INTERFACE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .85A.1 Comparison of Functions: LC

Seite 102 - A.4.2 View Alarm Log

System and Control Options529.5.7 Define Sensor as Alarmable or EventEach sensor may be defined as Alarmable (AL) or as an Event (EV).• For a sensor d

Seite 103 - A.4.3 View Event Log

System and Control Options539.5.9 Change Low SetpointThe Low Setpoint value is typically above the 4 mA value for the sen-sor. For example, if the 4 m

Seite 104 - A.4.4 View Trend Log

System and Control Options549.5.11 Set Up Delay TimeEach sensor may be set up with a specified time delay between the triggering of a high or low setp

Seite 105 - A.4.5 View Input Status

System and Control Options559.6 Setup System - Setup I/O MatrixThe Setup I/O Matrix menu allows you to configure the Universal Monitor’s digital and a

Seite 106 - A.4.6 View Output Status

System and Control Options56Map Input to Expansion Board Output• From the Select Outputs menu, select Map to Exp Board if you want to map the selected

Seite 107 - A.4.7 View Pager Numbers

System and Control Options579.6.2 Set Up Mapping for an Analog Sensor Input• Use the arrows ↑↓ to choose Map Sensor To Outpt from the Map Input/Sensor

Seite 108 - Main Menu

System and Control Options589.7 Setup System - Setup OutputThe Universal Monitor has eight outputs that may be configured indi-vidually. If the option

Seite 109 - Back Up Alarm Log File

System and Control Options599.7.3 Set Expansion Board Output by DIP SwitchIf you choose Change State from the Setup Output Menu for an Expansion Board

Seite 110 - Back Up Event Log File

System and Control Options609.8 Setup System - Setup Modem & PagersTo use the modem and pager features, be sure to connect the phone line connecto

Seite 111 - Back Up Trend Log Files

System and Control Options61Select Modem Setup4. From the Setup System Menu, shown at right, use the arrows↑↓ to choose Setup Modem&Pagers and pre

Seite 112 - A.6 SETUP MENU

vFIGURESFigure 1 Small enclosure—external features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Seite 113 - Setup Menu

System and Control Options629.8.2 Modem Setup - Additional Features (Service Terminal Interface only)The Service Terminal Interface offers four additi

Seite 114 - A.6.1 Setup Input

System and Control Options63Enable Modem Diagnostic MessagesEnabling modem diagnostics will provide the following additional information about the mod

Seite 115

System and Control Options649.8.3 Pager Setup - Pager Number and PINThe Universal Monitor may be configured to dial numeric or alphanumeric pagers whe

Seite 116 - A.6.2 Setup Common Alarm

System and Control Options65Enter a Pager Number• From the Setup Pager Menu, choose Setup Pager Number for the selected pager—Setup Pager 1 Number in

Seite 117 - A.6.3 Setup Sensor

System and Control Options669.8.4 Pager Setup - Communications Check (Service Terminal Interface only)The Service Terminal Interface offers two additi

Seite 118 - Setup Sensor (continued)

System and Control Options67Enable Communications CheckEnabling this function permits a daily communications test between the Universal Monitor and th

Seite 119 - A.6.4 Setup I/O Matrix

System and Control Options689.9 Setup System - Setup System InfoThe Setup System Info options allow users to:• Change Password—used for access to syst

Seite 120

System and Control Options699.9.1 Change PasswordA password is required to access the Universal Monitor’s system and control options, as described in

Seite 121

System and Control Options709.9.3 Setup Site IDYou may enter a Site ID to identify the Universal Monitor’s location, using a name that may consist of

Seite 122

System and Control Options719.9.5 Backup and Upload Configuration File (Service Terminal Interface only)This operation may be performed only through t

Seite 123

viTable 32 Service phone number dialing results . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74Table

Seite 124

System and Control Options72Back Up the Configuration File8. At the prompt to Initiate a Backup of Configuration File, enter Y (Yes - begin) or N (No

Seite 125 - A.6.5 Setup Output

System and Control Options73Upload the Configuration File13. At the prompt to Initiate an Upload of Configuration File, enter Y (Yes - begin) or N (No

Seite 126

System and Control Options749.9.6 Setup Serv Ph Num - Enter Phone NumberThe Service Phone Number (Serv Ph Num) is used for remote monitoring by Lieber

Seite 127 - Pager Setup

System and Control Options759.9.7 Setup Serv Ph Num - Communications Check (Service Terminal Interface only)The Service Terminal Interface offers two

Seite 128 - Modem Setup

System and Control Options769.9.8 Factory DefaultsAt any time, you may restore all default values for settings in the Uni-versal Monitor as it was shi

Seite 129 - Change Password

System and Control Options772. The firmware update is a two-step process—this step describes how to upload the file prog###.s19 (where ### is a number

Seite 130 - Setup Site ID

System and Control Options789.9.10 Initiate Remote Alarm Test (Service Terminal Interface only)The service phone number is used for remote monitoring

Seite 131 - Connect Battery

System and Control Options799.10 Setup Exp Board - Optional Expansion BoardBy default, the optional Expansion Board is configured as Not connected (N)

Seite 132 - Setup Service Phone Number

System and Control Options809.11 Manual Output CtrlThe Manual Output Ctrl feature allows you to manually change the state of any digital output to ON

Seite 133 - Factory Defaults

System and Control Options819.12 Clear Alarms & LogsThe Clear Alarms & Logs menu allows you to clear active alarms or delete all records from

Seite 134 - Initiate Remote Alarm Test

Introduction11.0 INTRODUCTIONThe Liebert Universal Monitor’s extensive capabilities can put it at the heart of your protective net-work. The Universal

Seite 135 - A.6.8 Connect Expansion Board

System and Control Options829.12.3 Clear the Event LogThe event log contains up to 99 records of events detected by the Uni-versal Monitor. You may wa

Seite 136 - A.6.9 Override Output

Specifications8310.0 SPECIFICATIONS10.1 Universal Monitor SpecificationsPowerRequirementsSmall Enclosure Large EnclosureNOTEUMS02400115VACUML11500230V

Seite 137

Specifications8410.2 Optional Expansion Board SpecificationsPowerRequirementsUMEXPNOTEIf the equipment isused in a mannernot specified by themanufactu

Seite 138 - Clear the Alarm Log

Service Terminal Interface85APPENDIX A- SERVICE TERMINAL INTERFACEThe Service Terminal Interface allows access to all functions of the Universal Monit

Seite 139 - Clear the Trend Logs

Connecting to the Service Terminal Interface86A.2 CONNECTING TO THE SERVICE TERMINAL INTERFACEThis section describes how to set up and connect to the

Seite 140

Connecting to the Service Terminal Interface87A.2.2 Create a ConnectionBefore connecting to the Service Terminal Interface, you must create a connecti

Seite 141

Connecting to the Service Terminal Interface88A.2.3 Set Up the COM1 Port - Direct Connection OnlyThe following steps apply only to setting up a direct

Seite 142

Connecting to the Service Terminal Interface89A.2.4 Set Up the Connection’s PropertiesThe following steps are needed for both direct and remote connec

Seite 143

Connecting to the Service Terminal Interface90A.2.5 Connect to the Service Terminal InterfaceAfter creating and setting up a connection, use a communi

Seite 144

Overview of Menus91A.3 OVERVIEW OF MENUSThe Main Menu offers choices for viewing the status of the Universal Monitor, silencing the audible alarm and