Liebert Cooling Modules XDH Bedienungsanleitung

Stöbern Sie online oder laden Sie Bedienungsanleitung nach Hardware Liebert Cooling Modules XDH herunter. Liebert Cooling Modules XDH User Manual Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken

Inhaltsverzeichnis

Seite 1 - User Manual - 50 & 60Hz

Precision CoolingFor Business-Critical Continuity™Liebert® XDH™User Manual - 50 & 60Hz

Seite 2 - GENERAL SAFETY GUIDELINES

General product information63.3.2 Unit HandlingIf possible, transport the unit using a forklift or pallet jack.• If using a forklift or pallet jack, e

Seite 3 - TABLE OF CONTENTS

General product information73.3.4 Taking the Unit off the Pallet1. Locate the ramp that was shipped with the Liebert XDH (see Figure 5).2. Loosen the

Seite 4

General product information8Figure 7 Attaching ramp, removing the Liebert XDH from palletTie-Down Bracket(removed from pallet)Bracket installed,securi

Seite 5 - XD H 32 B K —

Mechanical Considerations94.0 MECHANICAL CONSIDERATIONS4.1 Determining Placement in the Conditioned SpaceThe Liebert XDH units should be placed among

Seite 6 - 2.0 INTRODUCTION

Mechanical Considerations104.2.1 Airflow DirectionIf the Liebert XDH is installed at the end of a row, Liebert recommends using uni-directional air di

Seite 7 - 2.5.1 Room Preparation

Mechanical Considerations11Install Air Diffusers for Best Airflow Direction1. Remove the top diffuser, Part # 186458, from its packaging.2. Check the

Seite 8 - 3.2 Checking and Unpacking

Piping125.0 PIPING5.1 European Union Fluorinated Greenhouse Gas RequirementsStationary air conditioning, refrigeration, heat pump equipments and stati

Seite 9 - 3.3 Equipment Inspection

Piping13Figure 12 Typical Liebert XDH piping—non-interlaced connectionFigure 13 Direct system configuration—hydraulic system schematicDrawing is not t

Seite 10 - 3.3.3 Unpacking the Unit

Piping14Figure 14 Indirect system configuration—hydraulic system schematicLiebertXDPLiebert XD Cooling Module *Liebert XD Cooling Module *Building C

Seite 11 - General product information

Piping155.3 Connection Methods and PointsRefer to site specific drawings for general locations of the piping connections. For Liebert XDH con-nection

Seite 12

GENERAL SAFETY GUIDELINESFluorinated Greenhouse Gas Requirements—European UnionStationary air conditioning, refrigeration, heat pump equipme

Seite 13 - 4.0 MECHANICAL CONSIDERATIONS

Piping165.4 Piping Considerations—Hard-Piped ConnectionsRefrigerant enters and exits the Liebert XDH through connections on the top of the unit (see F

Seite 14 - 4.2.1 Airflow Direction

Piping175.4.2 Brazing PreparationsAfter the holding charge has been vented, a torch can be used to remove the caps over the ends of the supply and ret

Seite 15 - Top Diffuser, Part # 186459

Piping18Figure 17 Piping location and connecting sizes for pre-charged units5.7 Field Installation of Liebert XD Flex Pipe Kit on the Liebert XDHLiebe

Seite 16 - 5.0 PIPING

Piping195.8 Connecting Liebert XD Flex Pipes to Liebert XDH Modules1. Remove the caps on the supply and return lines on the top of the Liebert XDH.2.

Seite 17 - Liebert XDP /

Piping20Figure 19 Liebert XD prefabricated piping assembly6. Thread the return couplers together. The return couplers are the larger of the couplers.7

Seite 18

Piping21Figure 21 Liebert XD system with prefabricated piping assembly and Liebert XD Flex Pipe 5.10 Disconnecting a Liebert XDH With Liebert XD Flex

Seite 19 - Refer to Table 2 for details

Piping22Figure 22 Profile view of the Liebert XD system7. Place the protective dust cap and plug back onto both ends of the couplers on the Liebert XD

Seite 20 - Detail "A"

Electrical236.0 ELECTRICALThe unit must be installed in accordance with national wiring regulations. Refer to the unit’s serial tag for electrical req

Seite 21 - 5.6 Recommended Piping Size

Electrical246.2 Connecting Low Voltage Wiring—OptionalLow voltage connections to the Liebert XDH are available only on units with the optional condens

Seite 22 - Connection

Installation Checklist and System Fill for Startup257.0 INSTALLATION CHECKLIST AND SYSTEM FILL FOR STARTUP7.1 Checklist for Proper Installation___ 1.

Seite 23 - Tools Required

iTABLE OF CONTENTSGENERAL SAFETY GUIDELINES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . INSIDE FRONT COVER1.0 LIEBERT XDH C

Seite 24

Operation268.0 OPERATIONThe Liebert XDH’s controls are on the front of the unit at the Liebert XDH’s midline for easy access. Each switch controls the

Seite 25

Maintenance279.0 MAINTENANCEMinimal maintenance is required to keep the Liebert XDH operating at optimal levels. The unit should be cleaned and checke

Seite 26 - 5.11 Insulation

Maintenance289.3 Remove Fan Tray1. Ensure that all electrical power to the Liebert XDH has been shut off before beginning to remove the fan tray.2. Re

Seite 27 - 6.0 ELECTRICAL

Specifications2910.0 SPECIFICATIONSTable 3 Liebert XDH specificationsModelsXDH20DKP-0XDH20DK--0XDH20BKP-0XDH20BK--0XDH20DKPE0XDH20DK-E0XDH20BKPE0XDH20

Seite 28

Specifications30Table 4 Liebert XD Flex Pipe assemblies, supply and returnDescriptionLiebert P/NStraight ConnectionAssemblyLiebert P/N90-Degree Connec

Seite 30 - 8.0 OPERATION

Ensuring The High AvailabilityOf Mission-Critical Data And Applications.Emerson Network Power, the global leader in enabling business-criticalcontinui

Seite 31 - 9.0 MAINTENANCE

ii7.0 INSTALLATION CHECKLIST AND SYSTEM FILL FOR STARTUP . . . . . . . . . . . . . . . . . . . . . . .257.1 Checklist for Proper Installation . . . .

Seite 32 - 9.3 Remove Fan Tray

Liebert XDH Component Locations and Model Number Nomenclature11.0 LIEBERT XDH COMPONENT LOCATIONS AND MODEL NUMBER NOMENCLATUREFigure 1 Liebert XDH co

Seite 33 - 10.0 SPECIFICATIONS

Introduction22.0 INTRODUCTION2.1 Product DescriptionThe Liebert XDH cooling module is designed to be placed within a row of server enclosures in a hot

Seite 34

Introduction32.5 Installation ConsiderationsThe Liebert XDH is designed for placement within a row of computer cabinets in the data center in a hot-ai

Seite 35

General product information43.0 GENERAL PRODUCT INFORMATION3.1 Product/System DescriptionThe Liebert XDH is designed for placement within a row of com

Seite 36 - SL-17210_REV08_05-08

General product information53.3 Equipment InspectionUpon arrival of the unit, and before unpacking, verify that the labeled equipment matches the Bill