SITE MONITORINGSiteGate-232USER’S MANUAL
Rev. (08-JULY-98) © 1996-98 Liebert Corporation10CablesSeveral cables, which vary depending upon the communication requirements, are available. The
© 1996-98 Liebert Corporation11 Rev. (08-JULY-98)SiteGate-232Console Port #2Terminal Number TXRXGNDRXTXGND12345327No connection requiredNo conn
Rev. (08-JULY-98) © 1996-98 Liebert Corporation12Common ProblemsModem connected to the SiteGate-232 will not answer.Make sure the TR light on the mo
© 1996-98 Liebert Corporation13 Rev. (08-JULY-98)Figure 11: SiteGate-232 LED IdentificationRUN LED ERROR LED CONDITION2 flashes persec.Off All norma
Rev. (08-JULY-98) © 1996-98 Liebert Corporation14LED Power-up SequenceDuring power-up, the module goes through an initialization and self test seque
© 1996-98 Liebert Corporation15 Rev. (08-JULY-98)LGM Module DriverParameter PageFunction Block Type: LGM (LGM Module Driver)Name SiteGate-232
Rev. (08-JULY-98) © 1996-98 Liebert Corporation16 If not connected, and with no alarms pending delivery, reset modem every 5:00 (mm:ss). Note: t
© 1996-98 Liebert Corporation17 Rev. (08-JULY-98)Output character pacing? If set to YES, this parameter reduces CMnet transmission speed by 50%.Th
Rev. (08-JULY-98) © 1996-98 Liebert Corporation18Modem Control ParametersModem Reset: This is a user definable parameter that sends a reset string
© 1996-98 Liebert Corporation19 Rev. (08-JULY-98)Status PageFunction Block Type: LGM (LGM Module Driver)Name SiteGate-232 Line 1
Rev. (08-JULY-98) © 1996-98 Liebert Corporation2SiteGate-232Technical InstructionsContentsIntroduction...
Rev. (08-JULY-98) © 1996-98 Liebert Corporation20LGM Module Driver StatusThis is the overall module status.Function Block Type: This the Module Dri
© 1996-98 Liebert Corporation21 Rev. (08-JULY-98)Module Halted: All GFB related tasks have stopped. This can only happen if there have been 3 or mo
Rev. (08-JULY-98) © 1996-98 Liebert Corporation22Module time and date: Shows the current module date and time.Time since last reset: The amount of t
SiteGate-232 - User's ManualA World Leader in Computer Support SystemsEnvironmental Control • Power Protection • Site Monitoring/ControlServi
© 1996-98 Liebert Corporation3 Rev. (08-JULY-98)IntroductionThe SiteGate-232 is part of the Liebert SiteScan gateway family and provides communicatio
Rev. (08-JULY-98) © 1996-98 Liebert Corporation4Battery: Seven-year lithium battery provides a minimum of 10,000 hours of data retention duringpowe
© 1996-98 Liebert Corporation5 Rev. (08-JULY-98)segment. A segment is defined as the network of modules between main nodes. Main nodes can berepres
Rev. (08-JULY-98) © 1996-98 Liebert Corporation6Power WiringCAUTION: The SiteGate-232 modules are Class 2 devices (less than 30 VAC). Take appropr
© 1996-98 Liebert Corporation7 Rev. (08-JULY-98)Addressing, Baud Rates, and Console SettingsThe SiteGate-232 module's address is factory-set as
Rev. (08-JULY-98) © 1996-98 Liebert Corporation8Procedure1. Turn the SiteGate-232's power switch OFF.2. Set the module's baud rates and co
© 1996-98 Liebert Corporation9 Rev. (08-JULY-98)The "SETGCM" CommandThe "SETGCM" command initializes the SiteGate-232 with system
Kommentare zu diesen Handbüchern